Resources

Lightning risk assessment guides

Guides to the lightning protection standards Lumex™ runs, the risk methods behind every assessment, and how Lumex™ turns them into a report you can defend.

New to lightning risk? Start here

Five guides, in the order an engineer learns the method.

  1. Step 1

    What a lightning risk assessment decides

    Who needs one, where its numbers come from, and what the report must hold.

  2. Step 2

    The standard your project follows

    Pick the one that governs your site. Each has its own method.

  3. Step 3

    How a risk is calculated

    One example building, from the inputs to the pass or fail verdict.

  4. Step 4

    Protection levels and zones

    What the verdict asks of the protection you design.

  5. Step 5

    Designing the protection

    Air terminals, down conductors, earthing and surge protection, in order.

NFPA 780

United States. Annex L, from the simplified risk assessment to R1 to R4. How Lumex™ runs NFPA 780

Every standard

Guides that apply whichever standard your project follows.

Guides by country

How each country adopts the standard, and the national rules that change the numbers.

Guides by sector

Why the risk changes with what the building is for, under each standard.

Want to see the method run end to end? Read how an assessment works, clause by clause.

What Lumex™ does, and what stays with you

Lumex™ computes the method of the standard you choose, IEC 62305-2:2024, AS 1768:2021 or NFPA 780-2026, and shows the working. It does not certify a structure. You may not issue or submit a Lumex™ output until a competent person, qualified where the structure is located, has reviewed the inputs and the result and signed it.

The tolerable risk in IEC 62305-2 is not a fixed constant. Clause 7.3 NOTE 1 gives RT = 1 × 10⁻⁵ per year as a representative value of tolerable risk and adds that another value may be set once the case has been investigated in detail. The standard's introduction then lets national or local regulations fix RT, the tolerable frequency of damage FT, and the Annex A, B, C and E calculation rules and parameter values. Every IEC 62305-2 assessment in Lumex™ states the jurisdiction it was computed under and the values that applied.

Get started today

Guides for every standard, and software that replaces the spreadsheet