Free tool

Separation distance calculator

Work out the IEC 62305-3:2024 separation distance s, the gap a lightning protection system must keep from metal parts and wiring so a strike cannot spark across, and check the gap you have against it. Free, no sign-up, every coefficient cited.

Under IEC 62305-3:2024 the separation distance is s = (ki / km) × kc × l, equation (6). Any unbonded metal part or wiring must be more than s from the lightning protection system, or a strike can spark across.

Choose the class of LPS, the material across the gap and how the down conductors share the current, then enter the length l. The calculator runs the same calculation as a full Lumex™ assessment, on the values the 2024 edition publishes, and shows each coefficient with its table. Enter the gap you have and it tells you whether the gap is enough. For the full method, read the separation distance calculation guide.

The calculator

Separation distance, simplified approach

The page opens on the worked example below. Change any value to check your own point.

Your LPS and the gap

Class I Class II Class III Class IV
Table 11
Attached to the structure Isolated from the structure
clauses 3.3 and 3.4
Air Concrete, brick or wood Insulating stand-off (FRP, PE or PVC) Another material, manufacturer's k_m
Table 12
m
only for an insulating stand-off (Table 12 NOTE 1)
only for another material
the datasheet or test report
Table 13, by the number of down conductors A value from a detailed calculation (6.3.1 NOTE 2)
internal ones included
Type A, separate electrodes Type B, ring or foundation electrode
clauses 5.4.2.2 and 5.4.2.3
Type A only, in order round the building, for example 8, 10, 9, 12
only for a value from a detailed calculation
the calculation or programme
m
along the conductors to the nearest bonding point or earth
m
optional, to judge the gap
None of these Extensive metal framework Reinforced concrete, rods interconnected and verified Meshed earth termination, no accessible metal in the lightning path
clause 6.3.1
Separation distance s
0.2112 m
The distance provided, 0.5 m, is greater than s.
The separation distance applies to this structure. Sources: IEC 62305-3:2024 (Ed.3) Table 12; IEC 62305-3:2024 (Ed.3) Table 11; IEC 62305-3:2024 (Ed.3) Table 13; IEC 62305-3:2024 (Ed.3) 6.3.2 equation (6).
Quantity How it was found Value Source
k_iClass III0.04IEC 62305-3:2024 (Ed.3) Table 11
k_mAir1IEC 62305-3:2024 (Ed.3) Table 12
k_cby the number of down conductors, 40.44IEC 62305-3:2024 (Ed.3) Table 13
llength to the nearest bonding point or earth termination12IEC 62305-3:2024 (Ed.3) 6.3.2
s(k_i / k_m) × k_c × l = (0.04 / 1) × 0.44 × 120.2112 mIEC 62305-3:2024 (Ed.3) 6.3.2 equation (6)
ddistance provided, greater than s0.5 mIEC 62305-3:2024 (Ed.3) 6.3.1
The method

What each coefficient does

When lightning current runs down a conductor, the voltage along it rises with the length the current has travelled since the last bonding point. A metal pipe, a cable tray or a handrail nearby sits at a different potential, and if the gap between them is too short, the air or masonry breaks down and a spark jumps across. Clause 6.3 of IEC 62305-3:2024 sizes the gap that prevents it.

ki, the class of LPS. Table 11 sets ki by class. The stricter the class, the steeper the current it is designed for, so class I has the largest ki and needs the widest gap for the same layout.

km, the material in the gap. Table 12 gives air the reference value and concrete, brick and wood a lower one, which makes s larger: a solid wall breaks down more easily than the same thickness of air. Table 12 NOTE 1 adds a value for an insulating stand-off of FRP, PE or PVC, only from a set length upwards, and sends every other material to its manufacturer. Where several materials sit in series, NOTE 2 takes the lowest km.

kc, how the current divides. With several down conductors, each carries only a share of the current. Table 13 gives an approximate share by the number of down conductors, and a single down conductor is allowed only for an isolated LPS. For Type A earthing the note under Table 13 sets kc to 1 when neighbouring electrodes differ in resistance by more than a factor of 2, so the calculator asks for those resistances. A value from a detailed calculation may replace the table under clause 6.3.1 NOTE 2, with its source recorded.

l, the length. Measure it along the lightning conductors, air termination first, then down conductor, starting where you are checking and stopping at whichever comes first: a bonding point or the earthing. The longer the path, the larger s, which is why the gap needs to grow towards the top of a building. Clause 6.3.2 NOTE 1 lets the structure's height stand in for l on a building whose smaller plan dimension is no more than three times its height.

Sometimes no gap is needed. In a structure whose metal or reinforced concrete framework is electrically continuous, clause 6.3.1 drops the separation distance where a bonding network to IEC 62305-4 runs through the framework. Without that network the full distance still applies. The calculator checks this first, from the framework and bonding choices at the foot of the form.
Worked example

A pipe 0.5 m from a down conductor, 12 m above the earth termination

Illustrative inputs, not a real site: an attached class III LPS with 4 down conductors and Type B earthing, an air gap. The figures are computed live by the engine.

Equation (6) gives s = 0.2112 m. The pipe is 0.5 m away, more than s, so the gap is enough at that point. Higher up the same down conductor l grows, and so does s.

Quantity How it was found Value Source
k_iClass III0.04IEC 62305-3:2024 (Ed.3) Table 11
k_mAir1IEC 62305-3:2024 (Ed.3) Table 12
k_cby the number of down conductors, 40.44IEC 62305-3:2024 (Ed.3) Table 13
llength to the nearest bonding point or earth termination12IEC 62305-3:2024 (Ed.3) 6.3.2
s(k_i / k_m) × k_c × l = (0.04 / 1) × 0.44 × 120.2112 mIEC 62305-3:2024 (Ed.3) 6.3.2 equation (6)
ddistance provided, greater than s0.5 mIEC 62305-3:2024 (Ed.3) 6.3.1
The limits

What this calculator leaves out

This is the simplified approach of clause 6.3.2, one kc for the whole length. The general approach of clause 6.3.1, equation (5), splits the path into segments with a kc each, from the ring conductor and meshed air termination methods of Annex B, so it follows the real share of current in each part of the path. An electrically insulated LPS is judged on its manufacturer's equivalent separation distance instead. High installations need the altitude correction of clause 6.3.2, and a loop in a down conductor follows clause 5.3.4. The full assessment handles all of these.

Run the full assessment. Lumex™ records the down conductors, rings and electrodes of the actual layout, works every separation check from them on the same engine as this calculator, and puts the checks in the report with the class of LPS from the risk assessment. Start a free trial, or find the class with the lightning protection level selector. Lumex™ is independent of the IEC: buy the standard for design and certification.
FAQs

Questions answered

What is the separation distance in lightning protection?

It is the minimum gap, s, between the lightning protection system and nearby metal parts or electrical and electronic systems that are not bonded to it. If the gap is smaller, the voltage on a down conductor carrying lightning current can spark across it. IEC 62305-3:2024 clause 6.3 calculates s and asks for a distance greater than it.

How is the separation distance calculated?

The simplified approach of IEC 62305-3:2024 clause 6.3.2 uses equation (6): s = (k_i / k_m) × k_c × l. k_i depends on the class of LPS (Table 11), k_m on the insulating material in the gap (Table 12), k_c on how the lightning current divides between down conductors (Table 13 or Annex B), and l is the conductor length from the point you check, over the air termination and down the down conductor, to the first bonding point or the earthing.

What value of k_c should I use?

With the simplified approach, Table 13 of IEC 62305-3:2024 gives an approximate k_c by the number of down conductors, with a single down conductor allowed only for an isolated LPS. With Type A earthing the note under the table applies: where one electrode's resistance is over twice its neighbour's, k_c becomes 1. A value from a detailed calculation may be used instead under clause 6.3.1 NOTE 2, with its source recorded.

Does the material in the gap matter?

Yes. Table 12 of IEC 62305-3:2024 gives k_m for air and for concrete, brick and wood, and its NOTE 1 adds a value for an insulating stand-off of FRP, PE or PVC at least 0.5 m long. Any other material takes the value its manufacturer declares. Where several materials sit in series, NOTE 2 takes the lowest k_m, which gives the largest s.

When is no separation distance needed?

Clause 6.3.1 of IEC 62305-3:2024 covers a structure whose metal or reinforced concrete framework is electrically continuous. If a bonding network to IEC 62305-4 is installed through it, no separation distance is required. If the framework only acts as natural down conductors without that bonding, the full separation distance applies. Choose the framework and tick the bonding network in the calculator to apply the rule.

Is d equal to s enough?

No. Clause 6.3.1 asks for a distance greater than s, so a gap exactly equal to s does not pass. The exception is a loop in a down conductor, where clause 5.3.4 asks only that the two points be no less than s apart. The full Lumex™ assessment handles loops as their own checks.

Does this match the Lumex™ product?

Yes. The calculator runs the same separation distance calculation as a full Lumex™ assessment, on the same Table 11, 12 and 13 values, and shows its refusals and warnings word for word. The product adds the general approach of equation (5), the Annex B figures and a check for every point on the layout.

Get started today

Every separation check on the building, worked from the layout and kept in the report