Earthing guide

Earthing and the earth-termination system in IEC 62305-3

The earth termination is the last link in a lightning protection system: the part that takes the strike current the air terminations caught and the down conductors carried, and pushes it safely into the soil. This guide explains what it does, the electrode arrangements IEC 62305-3 describes, why a low and stable earth resistance matters, and why earthing is measured again at every complete inspection.

Rooftop electrical enclosures, conduit and a solar array, the services that surge protection and bonding look after

The earth-termination system is the part of a lightning protection system that pushes the strike current into the ground.

It is the set of earth electrodes, rings or foundation steel that the down conductors connect to, and its one job is to spread the captured current into the soil quickly and safely. Under IEC 62305-3 a good earth termination has a low and stable earth resistance and is arranged so the current leaves the structure with the smallest possible rise in potential.

It is easy to treat earthing as an afterthought, a rod in the ground at the bottom of a down conductor, but it is the link the whole system ends on. The air terminations catch the strike and the down conductors carry it down; if the earth termination cannot then get rid of the current cleanly, the rest of the work is undone. This guide explains what the earth termination does, the two electrode arrangements IEC 62305-3 describes, why earth resistance and soil conditions decide the design, why a single bonded earthing system is shared with power and telecoms, and why the earth resistance is read at every complete inspection rather than once. If you design to NFPA 780-2026 in the US or AS 1768:2021 in Australia, a section near the end sets out what your own standard asks of the earthing.

The job it does

What the earth termination is for

A lightning strike delivers a very large current in a very short time. The external lightning protection system gives that current a controlled path: the air termination catches it, the down conductors carry it down the structure, and the earth termination takes it from the bottom of the down conductors and dissipates it into the soil. The earth termination is where the energy finally leaves the building, so the quality of the earthing decides how cleanly the whole system performs.

While the current is flowing into the ground, the electrode and the soil around it rise to a high voltage. The faster and more evenly the current spreads away, the smaller that rise in potential is. A small rise is what keeps the rest of the system safe: it limits side flashing, where the high voltage on the earthing arcs across to nearby buried metal or services, and it keeps the step and touch voltages in the ground near the building small enough not to hurt anyone standing there. A sluggish earth termination, by contrast, holds the structure at a high potential for longer and pushes both of those hazards up.

The earthing is the end of one chain. Air termination, down conductors and earth termination work as a single path: catch the strike, route it down, dissipate it into the soil. A weakness in the earthing undoes the strength of everything above it, which is why the earth termination is designed, measured and maintained as carefully as the parts on the roof.
Electrode arrangements

Type A and Type B earth electrodes

IEC 62305-3 describes two ways of arranging the earth electrodes. They are not ranked best to worst; each suits a different kind of building, and they can be combined on one site.

Type A

Individual electrodes at each down conductor

Separate electrodes, vertical rods driven into the ground or horizontal strips laid in a trench, connected to each down conductor but not joined together in a loop. The arrangement is simple and easy to retrofit, which is why it suits small, low-rise and uncomplicated structures. Each electrode does its work locally, so the design depends on getting enough electrode length into the soil at every down conductor.

Type B

A ring or foundation earth around the structure

A closed loop instead of separate rods: either a ring electrode buried around the outside of the structure, or a foundation earth electrode formed in the concrete foundations. The loop ties all the down conductors to one earth and gives a more even ground potential under and around the building. It suits larger structures and any building with sensitive electronics inside, where that even potential matters most.

The recommended electrode lengths for each arrangement, and how they change with the lightning protection class and the soil, are given in the standard itself. The principle to carry away is the difference in shape: Type A is a set of local electrodes, Type B is one continuous loop, and the loop is what produces the even, well-coupled earth that larger and more sensitive buildings need.


Choosing between them

When each arrangement suits

The choice follows from the size of the structure, what it contains, and the ground it stands on, not from preference.

Type A for small, simple buildings

Low-rise structures, small footprints and retrofits where a continuous ring is impractical. Individual rods or strips at each down conductor are enough to dissipate the current, and they are the easiest to add to an existing building.

Type B for larger and sensitive structures

Bigger buildings, and any structure holding electronic systems that a difference in ground potential could disturb. The ring or foundation earth ties everything to one equipotential earth, which is exactly what those systems need.

Foundation earth for new builds

A foundation earth electrode cast into the concrete is a Type B arrangement that is durable, protected from corrosion and well-coupled to the soil. Designed in at the start, it gives a strong earth at little extra cost and is hard to better as a retrofit.

In practice the two are often mixed: a structure on difficult ground might use a foundation earth ring supplemented with vertical rods where the soil allows, so the arrangement matches both the building and the site rather than following one rule everywhere.

Earth resistance

Why a low, stable value matters

The single figure that describes how well an earth termination works is its earth resistance: how easily the electrode lets current spread away into the soil. A low and stable resistance lets the strike current dissipate quickly, so the voltage the electrode rises to during the strike stays modest. That smaller rise in potential is what keeps side flashing unlikely and keeps the step and touch voltages in the surrounding ground small. A high resistance does the reverse, holding the structure at a higher potential for longer and raising both hazards.

A value of 10 ohms is the figure most people quote, and it does come from IEC 62305-3:2024. Clause 5.4.1 recommends keeping the earth resistance below 10 ohms where that is achievable, so for most buildings it is a recommendation rather than a hard rule. It also does two specific jobs. For a Type A arrangement, reaching under 10 ohms lets you set aside the minimum electrode lengths of Figure 5 (clause 5.4.2.2). For a structure with explosive materials or hazardous areas, 10 ohms becomes a firm upper limit (clause C.2.3). Otherwise the standard steers you to electrode length and arrangement: Figure 5 gives the minimum length for the LPS class and the soil resistivity, and a reading above 10 ohms at inspection is a prompt to check the electrodes against that figure (clause D.7.3).

A target backed by length. IEC 62305-3 recommends under 10 ohms where possible and backs that with minimum electrode lengths, set against the protection class and soil resistivity in Figure 5. Only structures with explosive materials or hazardous areas have 10 ohms as a firm limit. A low, stable resistance is the goal; the electrode geometry is how the standard reaches it.

Ground conditions

Soil resistivity and why it shapes the design

The same electrode gives a very different earth resistance in different ground, because the soil itself is part of the circuit. Soil resistivity measures how strongly the ground resists current spreading through it, and it varies widely with soil type, moisture and temperature. Rock, sand and dry ground are high-resistivity and make a low earth resistance hard to reach; clay and consistently moist soil are low-resistivity and make it easier. The same rod that gives an easy low reading in damp clay can give a poor one in dry sand a short distance away.

Because of this, earthing design starts from a measurement of the site's soil resistivity rather than an assumption. Difficult, high-resistivity ground calls for the design to compensate: longer electrodes that reach deeper, moister soil, more electrodes spread out, or a ring or foundation earth that couples to a larger volume of ground. Resistivity also shifts with the seasons, drier in a long summer and after frost, which is one reason a single reading taken once is not enough to characterise a site for the life of the system.

The ground is part of the design. Two identical buildings on different soils need different earthing. This is why the standard works from soil resistivity and electrode length rather than prescribing one electrode for everyone: the design has to match the ground it sits in, and that ground is measured, not guessed.

One earth

A single bonded earthing system, shared with power and telecoms

A frequent and dangerous instinct is to give lightning its own separate earth, kept apart from the earthing used by power and telecoms. IEC 62305-3 favours the opposite: a single earthing system that serves the lightning protection and is bonded together with the power and telecoms earthing into one. A foundation or ring earth is well suited to being that shared earth, since it already runs around the whole structure.

The reason is straightforward. During a strike the lightning earth is lifted to a high potential for a fraction of a second. If the power and telecoms earths were kept separate, they would stay near their normal voltage, and that large difference in potential would force a flashover between the two earthing systems, often straight through equipment. Bonding everything to one earth removes the difference: the whole installation rises and falls together, so there is no gap in voltage for current to jump across. This is the same equipotential bonding principle that runs through the internal protection of the structure, applied at the earthing.


Protection of life

Step and touch voltage at the earth termination

The earthing is also where two hazards to people are created and controlled. When the strike current spreads out from the electrode, the ground around it sits at different potentials at different distances. Someone standing there can be exposed to a step voltage, between two feet a stride apart on ground at different potentials, and someone touching a down conductor near the ground to a touch voltage, between their hand and their feet. A low earth resistance and an even, well-coupled earth keep both small, which is one more reason the earthing arrangement matters beyond simply getting rid of the current.

A meshed earthing arrangement near the surface helps here, because it makes the ground rise in potential more evenly, so the difference between two nearby points stays small. Step and touch voltage protection is part of the wider Part 3 work, alongside insulation, barriers and signage at the down conductors. For how the standard handles the hazard to life in full, see the IEC 62305-3 guide to the LPS and its inspection.


Over time

Why earth resistance is measured at every complete inspection

An earth termination is correct on the day it is installed and then spends years buried in ground that changes around it. The value that describes it, the earth resistance, drifts. Electrodes and their connections corrode where metal meets soil. Joints loosen. The soil dries out in a long summer, pushing the resistance up until the next wet season. Construction nearby disturbs the ground, cuts a buried conductor or changes the moisture around an electrode. None of this is visible from the surface, and any of it can quietly raise the resistance past the point where the earthing still does its job.

This is why IEC 62305-3:2024 (Ed.3) puts electrical testing in every complete inspection (D.7.2.2), and that testing includes earth resistance measurement (D.7.3), rather than leaving it read once at handover and trusted forever. The yearly visual inspection does not measure it. A single good reading on the day of install proves only that the earthing was sound that day. The value of the measurement comes from comparing it across successive inspections, and D.7.3 asks for an investigation when the value changes significantly: a slow rise from one inspection to the next is the early sign of corrosion or a drying-out problem, caught while it is still a maintenance item rather than after it has become a real loss of protection. The earth resistance reading sits in the inspection report next to the continuity and bonding checks, and read in sequence those readings are the record of whether the earthing has held up.

A trend, not a snapshot. One earth resistance reading is a snapshot; the sequence of readings across inspections is what tells you whether the earthing is degrading. This is why the figure is recorded at each complete inspection and compared with the last, and it is a core part of the periodic inspection that keeps an installed system valid.
Under NFPA 780 and AS 1768

Earthing for lightning protection under NFPA 780 and AS 1768

The US and Australian standards aim at the same result by their own rules. Read each value from its own standard: a figure from IEC 62305-3 never applies to an NFPA 780 or AS 1768 design, and the reverse holds too.

Topic NFPA 780-2026 AS 1768:2021
Where a down conductor endsAt its own dedicated lightning grounding electrode or electrodes, or at a building electrode system joined by a ground ring electrode (4.12.1.1)Each dedicated downconductor is bonded to an earth electrode (3.5.2(b))
Electrode formsGround rods, concrete-encased electrodes in new construction only, a ground ring, radials, plates, or a mix of these (4.12.2 to 4.12.7)Conductors and earth electrodes, natural parts of the structure below ground such as reinforced concrete footings and steel piles, or both (3.5.1, 3.5.2)
Key minimumsRods at least 1/2 in. (12.7 mm) across and 8 ft (2.4 m) in length (4.12.2.1); a ground ring at least 18 in. (450 mm) deep in direct contact with earth, or cast in a concrete footing (4.12.4.1)Horizontal electrodes buried 500 mm or more beneath finished ground level (3.5.2(c)); aluminium conductors never buried directly (3.5.1)
Earth resistanceNo target value for the lightning grounding system; Annex B treats a low reading as helpful rather than essential (B.4.3, B.4.4)Should be 10 ohms or less before bonding to services outside the LPS, or the lowest practical value where soil prevents it (3.5.3)
Joining other earthsAll building grounding electrode systems are interconnected, including electric service, communications and antenna electrodes (4.13.3)All earthing systems of the structure are bonded to the earth termination network, directly or through gas discharge devices (3.5.2(a)), and to the electrical earth electrode (3.5.2(e))
Measuring it laterA complete inspection includes ground resistance tests, compared with earlier results (D.1.3, informative)Readings recorded during construction (3.5.3) and taken again in the maintenance program (5.4.2(d))

NFPA 780-2026. The electrode rules sit in Section 4.12 and the bonding of other grounded systems in Section 4.13. The standard prescribes the electrode rather than a reading. The site and its soil decide which electrode types you use (4.12.8). In sandy or gravelly ground with high resistivity, you add more electrodes (4.12.8.2). Where topsoil is shallow, a ring, radials or plates go in at the deepest the topsoil allows (4.12.8.1.1), and on bare bedrock radials or a loop conductor may be laid on the rock itself (4.12.8.1.3). Pipes and rods that belong to the electrical or communications systems cannot stand in for lightning electrodes (4.12.1.3), and Annex A prefers one interconnected grounding system for every service (A.4.12.1.1(2)). For the full set of rules, read NFPA 780 grounding and bonding.

AS 1768:2021. Section 3.5 calls the earthing the earth termination network. Its main job is to dissipate the strike energy, and it should also keep step and touch voltages low inside the structure and near it (3.5.1). Concrete and steel foundations usually serve once they meet the resistance clause, with dedicated electrodes bonded to the foundation steel where they do not (3.5.1). Beyond the firm requirements, the standard recommends joining multiple vertical electrodes together and labelling accessible dedicated electrodes so nobody disconnects them (3.5.2). Testing looks at the network as a whole: it should read under 10 ohms, while a single electrode within it may read higher (5.2(b), 5.2(c)). For the detail, read AS 1768 earthing.

Three standards, three rules on resistance. IEC 62305-3:2024 recommends under 10 ohms where possible (5.4.1). AS 1768:2021 recommends 10 ohms or less before service bonding (3.5.3). NFPA 780-2026 sets no figure at all. Check an earthing design against the standard it was built to. Lumex™ runs the risk assessment under each standard (see NFPA 780 in Lumex™ and AS 1768 in Lumex™). The earthing design stays with the engineer.

In context

Where earthing fits in IEC 62305

Earthing is the foundation of the physical protection that Part 3 describes, but it only exists because the Part 2 risk assessment decided the structure needed a lightning protection system and set the class it should be built to. The class feeds straight into the earthing: it influences the recommended electrode length and the arrangement, so the earth termination cannot be judged against a generic checklist, only against the class the structure was designed to. To see how the parts of the standard fit together, start with what IEC 62305 is, and for the full physical system and the inspection that keeps it valid, see the IEC 62305-3 guide.

The class the earthing is built to comes from the assessment. Lumex™ computes the IEC 62305-2 risk assessment (2024 edition) and reports the lightning protection level, which is what sets the earthing requirements in Part 3. Designing the earth termination, and the readings that verify it, stay with the engineer on site. When you are ready, run an assessment.
FAQs

Questions answered

What is the earth-termination system in lightning protection?

The earth-termination system is the part of a lightning protection system that dissipates the strike current into the ground. It is the set of earth electrodes, rings or foundation steel that the down conductors connect to, and its job is to spread the captured current into the soil quickly and safely. Under IEC 62305-3 a good earth termination has a low and stable earth resistance and is shaped so the current leaves the structure with the smallest possible rise in potential, which limits side flashing and the step and touch voltages near the building.

Do NFPA 780 and AS 1768 set a 10 ohm earth resistance?

AS 1768 recommends one and NFPA 780 does not. AS 1768:2021 Clause 3.5.3 says the earth termination network should be at 10 ohms or less before it is bonded to other services, and asks for the lowest practical value where the soil rules that out. NFPA 780-2026 sets no resistance target for the lightning grounding system. It prescribes electrode types, sizes and depths instead (Section 4.12), and its Annex B treats a low reading as helpful rather than essential (B.4.4).

What are Type A and Type B earth electrodes in IEC 62305-3?

IEC 62305-3 describes two earth-electrode arrangements. Type A uses individual electrodes, vertical rods or horizontal strips, connected to each down conductor but not joined together in a ring. Type B is a closed loop: either a ring electrode running around the outside of the structure, or a foundation earth electrode formed in the building's concrete foundations. Type B gives a more even potential under and around the building and is preferred for larger structures and for protecting internal systems, while Type A suits small, simple buildings.

When should you use a Type A or a Type B earth electrode?

Type A, individual rods or strips at each down conductor, suits small structures, low-rise buildings and retrofits where a continuous ring is impractical. Type B, a ring or foundation earth, suits larger buildings, structures with sensitive electronic systems inside, and any case where an even ground potential matters, because the loop ties all the down conductors to one equipotential earth. New buildings increasingly use a foundation earth electrode cast into the concrete, which is a Type B arrangement that is durable and well-coupled to the soil.

Why does a low earth resistance matter for lightning protection?

A low and stable earth resistance lets the strike current spread into the soil quickly, so the voltage the electrode rises to during the strike stays modest. That smaller rise in potential means less risk of side flashing to nearby metalwork, and smaller step and touch voltages in the ground around the electrode. A high resistance does the opposite: it holds the structure at a higher potential for longer and raises the hazard to anyone nearby. IEC 62305-3 recommends under 10 ohms where possible, and backs that with minimum electrode lengths for the class and soil in Figure 5.

Does IEC 62305 require a 10 ohm earth resistance?

Not as a general rule. IEC 62305-3:2024 clause 5.4.1 recommends an earth resistance below 10 ohms where possible, so for most buildings it is a target, not a pass mark. It becomes a firm maximum for structures with explosive materials or hazardous areas (clause C.2.3). For a Type A arrangement, getting under 10 ohms also means the Figure 5 minimum electrode lengths no longer have to be met (clause 5.4.2.2). Where 10 ohms cannot be reached, the standard asks you to meet the Figure 5 lengths for the class and soil instead.

How does soil resistivity affect earthing design?

Soil resistivity is how strongly the ground resists current spreading through it, and it varies widely with soil type, moisture and temperature. Rock, sand and dry ground are high-resistivity and make a low earth resistance hard to reach; clay and moist soil are low-resistivity and make it easier. Because the same electrode gives very different resistance in different ground, the earthing design starts from a measurement of the site's soil resistivity, and difficult ground needs longer electrodes, more of them, or a ring or foundation earth to reach a low, stable value.

Should the lightning earth be separate from the power and telecoms earth?

No. IEC 62305-3 favours a single earthing system that is shared and bonded with the power and telecoms earthing rather than a separate lightning earth. If the lightning earth were kept apart, a strike would lift it to a high potential while the other earths stayed low, and the difference would force a dangerous flashover between them. Bonding everything to one earth means the whole installation rises and falls together during a strike, with no difference in potential for current to jump across.

Why is earth resistance measured again at every complete inspection?

Because the value drifts. Electrodes corrode, connections loosen, soil dries out over a long summer or is disturbed by construction nearby, and any of these can raise the earth resistance without anyone noticing. A single good reading on the day of handover is no guarantee of a good reading years later. Under IEC 62305-3:2024 (Ed.3) the complete inspection includes electrical testing (D.7.2.2), testing includes earth resistance measurement, and a significant change from earlier values calls for investigation (D.7.3). Comparing readings across inspections catches a slow rise before it becomes a real loss of protection.

What Lumex™ does, and what stays with you

Lumex™ computes the method of the standard you choose, IEC 62305-2:2024, AS 1768:2021 or NFPA 780-2026, and shows the working. It does not certify a structure. You may not issue or submit a Lumex™ output until a competent person, qualified where the structure is located, has reviewed the inputs and the result and signed it.

The tolerable risk in IEC 62305-2 is not a fixed constant. Clause 7.3 NOTE 1 gives RT = 1 × 10⁻⁵ per year as a representative value of tolerable risk and adds that another value may be set once the case has been investigated in detail. The standard's introduction then lets national or local regulations fix RT, the tolerable frequency of damage FT, and the Annex A, B, C and E calculation rules and parameter values. Every IEC 62305-2 assessment in Lumex™ states the jurisdiction it was computed under and the values that applied.

Get started today

Earthing inputs and risk in one assessment, not two spreadsheets