Standards

NFPA 780-2026 risk assessment, from Annex L to signed report

Lumex™ runs the complete Annex L procedure of NFPA 780-2026, the current edition, on Sphera: the simplified risk assessment first, then the detailed assessment when the numbers call for it, with every figure traced back to its clause.

A laptop showing an NFPA 780-2026 risk assessment on a rooftop at night, beside a hard hat, with lightning over the city

Lumex™ runs the full NFPA 780-2026 Annex L procedure, from the simplified risk assessment to four risks judged apart.

What Lumex™ does with this standard

A commercial building facade with rooftop plant, the kind of structure an NFPA 780 risk assessment covers
Standard

Annex L, informative

NFPA 780-2026 is the Standard for the Installation of Lightning Protection Systems. Its risk assessment sits in Annex L, which guides the decision to protect and is not a requirement.

Simplified

The simplified risk assessment

The simplified risk assessment settles the clear cases in moments. Lumex™ runs it in full, not a shortcut, and shows the working behind every figure.

Detail

The detailed assessment

When the numbers are close, it works out up to four risks from eight components and judges each on its own (NFPA 780-2026 L.6.3).

Compare

NFPA 780 or IEC 62305

New to NFPA 780 itself? See how it compares with IEC 62305, then read on for how Lumex™ computes it.

L.5 and L.6

Two methods, one annex

The simplified risk assessment decides fast. The detailed assessment goes deeper when that is not enough on its own.

L.5 · simplified

The simplified risk assessment

Compares the expected strikes to the structure per year, ND, with a tolerable strike frequency NC built from the structure's own coefficients. An LPS is recommended when ND is higher than NC, and optional when it is not.

L.6 · detailed

The detailed assessment

Works out eight risk components from the structure and its connected services, then rolls them into up to four risks, R1 to R4, one for each kind of loss that applies to the structure (L.6.3). Each risk is judged on its own, never as a single combined number.

Behind L.5

What ND and NC are built from

Both sides of the comparison come from the standard's own coefficients, never a guess.

NSG

Lightning ground strike-point density

Read from the Vaisala strike-density map. Where only the flash density is known, Lumex™ converts it to strike points on the ground, the density the 2026 edition asks for.

AD

The structure's collection area

The equivalent area around the structure that attracts a strike, built from its dimensions, which turns the strike density into ND, the expected strikes per year.

C2 to C5

Construction, contents, occupancy, consequence

Four coefficients describing what the structure is built from, what it holds, who uses it and what a strike would cost. Together they set NC, the tolerable strike frequency it is judged against.

A critical facility, a hospital, a fire station or a power plant among them, should be protected or carried through the detailed assessment whatever the simplified risk assessment shows. That clause applies on top of the assessment, not instead of it.

L.6.2 & L.6.3

Four kinds of loss, each judged on its own

The detailed assessment never sums the risks into one verdict. R1 to R3 each meet their own tolerable line from Table L.6.2, R4 meets a value the owner enters, and a structure can fail on one while passing the rest.

R1 · life or injury

Loss of life or injury

Judged against the default tolerable value in Table L.6.2, the strictest of the four. The owner or the authority having jurisdiction may set a different value.

R2 · service

Loss of service

The risk that a strike interrupts a service the structure depends on, defaulting to the tolerable value in Table L.6.2.

R3 · historical significance

Loss of historical significance

For a structure of historical or cultural value, judged against its default tolerable value in Table L.6.2, the same default as loss of service.

R4 · economic value

Loss of economic value

The annex sets no default tolerable value here. Lumex™ still computes R4 and reports it, and judges it against a value only if the owner enters one.

L.6.4 & Table L.6.6

Eight components, from the structure and its services

Every risk is built from these eight components, each a source of strikes paired with what it puts at stake.

Component Where the strike lands
RA, RB, RCA direct strike to the structure itself
RMA strike near the structure, not a direct hit
RU, RV, RWA direct strike to a connected service, summed per service
RZA strike near a connected service, summed per service

The four kinds of loss are built from whichever of these eight components apply to that loss. Nothing here is summed into one number Lumex™ compares against a single line: R1 to R4 stay apart, all the way to the verdict.

Worked example · NFPA 780-2026

A small metal building, settled by the simplified risk assessment

An illustrative structure, computed by Sphera through the simplified risk assessment, with each step named by its clause.

The inputs

20 m by 15 m, 6 m high, standing alone

  • Lightning ground strike-point density NSG of 2 per km² per year (L.2), isolated, so CD is 1 (Table L.4.2)
  • Metal structure with a metal roof: C2 of 0.5
  • Low-value contents: C3 of 0.5. Normally unoccupied: C4 of 0.5
  • Services can stop without harm: C5 of 1.0 (Tables L.5.1.2(a) to (d))
The verdict (L.5.2.1)

ND is below NC, so an LPS is optional

  • Collection area AD of about 2,578 m², equation (L.4.1.1)
  • Expected strikes ND of 0.0052 per year, equation (L.3)
  • C = C2 × C3 × C4 × C5 = 0.125, so the tolerable NC is 1.5 × 10⁻³ ÷ 0.125 = 0.012 per year (L.5.1.1)
  • 0.0052 does not exceed 0.012, so protection is optional

Had ND come out above NC, an LPS would be recommended, and a critical facility goes on to the detailed assessment whatever the comparison shows. The values are illustrative; your figures depend on your own structure and site.

The report

What goes into the document you sign

One assessment produces a report carrying the verdict, the simplified risk assessment with its working, and the detailed assessment broken into the strikes to and near the structure, the risk components, the probabilities and shielding factors, and the loss factors behind each figure.

Where a proposed upgrade is worth checking, Lumex™ can show the risks with that protection in place alongside the risks as they stand today. The proposal is a Lumex™ feature, not a step of NFPA 780-2026, and it never changes the verdict, which always follows the protection actually in place.

A closing section states how the assessment was made, and every clause, equation and table the report cites is NFPA 780-2026. Lumex™ is an independent product and is not affiliated with or endorsed by the NFPA; the values shown here are illustrative, and the authoritative annex is defined in NFPA 780, available from the NFPA.

Read a full report before you start a trial: a worked example for an office block in Tampa, computed to NFPA 780-2026 through the simplified risk assessment and the detailed assessment.

Download the sample report

After the assessment

Know when each site is due for a look

Protection has to be checked for as long as it stands. Track the protection installed after an approved assessment, and Lumex™ keeps its inspection due dates from the intervals the standard gives.

Ask about inspections
  1. Available today

    Review dates, inspection dates and reminders

    The engineer sets when an assessment is looked at again. Each tracked protection system keeps its own inspection due dates. An email goes out two months before each date and again on the day.

  2. Available today

    Periodic inspection reports

    Plan each visit, then record the checklist, the readings at each test point and any defects. A reviewer signs it off, and you issue the inspection report and the protection system's evidence pack.

Lumi, the Lumex™ assistant

Lumi speeds the routine. Sphera still owns every number

You just read that procedure, computed clause by clause. Lumi works around Sphera to cut the busywork, with the signing engineer in control at every step.

Analysis

Risk-driver analysis

Reads the completed assessment and shows which component drives each risk, so you know exactly where to act.

Reporting

Drafted report narrative

Turns your computed figures into clear report prose you review, edit and approve before it is filed.

Mitigation

The least protection that complies

Tries combinations of protection measures and proposes the one that brings R1 to R4 within their tolerable values, with each risk before and after.

FAQs

NFPA 780-2026 in Lumex™, questions answered

Which edition of NFPA 780 does Lumex™ run?

NFPA 780-2026, the current edition. Lumex™ runs the risk assessment in its Annex L, both the simplified risk assessment and the detailed assessment, using the annex's own equations and tables, and every clause the report cites is from the 2026 edition. Annex L is informative, so whether an assessment is needed is for the owner, an insurer or the authority having jurisdiction to decide. See NFPA 780 Annex L explained.

What do I enter for an NFPA 780 assessment?

For the simplified risk assessment, two groups: the structure and its location, including the lightning ground strike-point density, then its construction, what it holds, who is inside and what a strike would lead to. Switch on the detailed assessment and four more groups follow: the protection in place, the shielding of the structure and its wiring, the connected services, and the losses that apply. Lumex™ checks each answer before it computes anything.

What is the difference between the simplified and the detailed assessment?

The simplified risk assessment (L.5) compares the expected strikes to the structure per year, N_D, with a tolerable strike frequency N_C built from four coefficients. The detailed assessment (L.6) works out eight risk components from the structure and its services and rolls them into up to four risks, R1 to R4, each judged on its own (L.6.3).

When should I run the detailed assessment?

When the simplified risk assessment is close, or when the facility should not rest on a shortcut. A critical facility, such as a hospital, a fire station or a power plant, should be protected or carried through the detailed assessment whatever the simplified risk assessment shows (L.5.3). You switch the detailed assessment on in the Simplified risk assessment step, and the report then prints both workings one after the other.

What tolerable values does Lumex™ use?

The annex defaults in Table L.6.2, one tolerable value per year for each of R1, loss of life or injury, R2, loss of service, and R3, loss of historical significance. R4, economic value, has no default, so Lumex™ reports it and judges it only if the owner enters a value. The owner or the authority having jurisdiction may set different values, and Lumex™ takes those as data.

Does Lumex™ recommend the protection?

Yes. It tries the measures the engineer controls, such as the physical damage and surge protection levels, re-runs the assessment for each set, and recommends the smallest set that brings every judged risk within its tolerable value (L.6.5), with the risks it leaves shown beside it.

How is the NFPA 780 engine checked?

Sphera is tested against nine cases computed by a separate implementation of Annex L, written from the annex's equations and tables rather than from the engine, and the two must agree to within rounding. Every figure in a result names the clause, equation or table it came from, so a reviewer can check it against the annex.

What goes into the NFPA 780 report?

The full report opens with the verdict, then lists what was entered, the simplified risk assessment with its working, and the detailed assessment where you ran one. It shows any protection you proposed beside the protection in place, the protection Lumex™ recommends, a note on how the assessment was made, and a calculation trace naming the clause behind each figure. The short report carries the verdict and your site photographs.

When is an NFPA 780 assessment due for review?

When the engineer says. Annex L sets no interval for redoing the assessment, so the engineer sets the review date on the assessment and gets an email two months before it and again on the day. The protection itself is inspected every year under Section 1.7, and Lumex™ keeps those inspection due dates on the protection system you track.
What Lumex™ does, and what stays with you

Lumex™ computes the method of the standard you choose, IEC 62305-2:2024, AS 1768:2021 or NFPA 780-2026, and shows the working. It does not certify a structure. You may not issue or submit a Lumex™ output until a competent person, qualified where the structure is located, has reviewed the inputs and the result and signed it.

NFPA 780-2026 Annex L gives default tolerable values of 1 × 10⁻⁵ per year for loss of life or injury and 1 × 10⁻³ for loss of service and of historical significance, and the owner or the authority having jurisdiction may set others. Every NFPA 780 assessment in Lumex™ states the values that applied.

Get started today

NFPA 780 Annex L worked out for you, not typed into a workbook