NFPA 780-2026 risk assessment, from Annex L to signed report
What Lumex™ does with this standard
Annex L, informative
NFPA 780-2026 is the Standard for the Installation of Lightning Protection Systems. Its risk assessment sits in Annex L, which guides the decision to protect and is not a requirement.
The simplified risk assessment
The detailed assessment
When the numbers are close, it works out up to four risks from eight components and judges each on its own (NFPA 780-2026 L.6.3).
NFPA 780 or IEC 62305
New to NFPA 780 itself? See how it compares with IEC 62305
Two methods, one annex
The simplified risk assessment decides fast. The detailed assessment goes deeper when that is not enough on its own.
The simplified risk assessment
Compares the expected strikes to the structure per year, ND, with a tolerable strike frequency NC built from the structure's own coefficients. An LPS is recommended when ND is higher than NC, and optional when it is not.
The detailed assessment
Works out eight risk components from the structure and its connected services, then rolls them into up to four risks, R1 to R4, one for each kind of loss that applies to the structure (L.6.3). Each risk is judged on its own, never as a single combined number.
What ND and NC are built from
Both sides of the comparison come from the standard's own coefficients, never a guess.
Lightning ground strike-point density
The structure's collection area
The equivalent area around the structure that attracts a strike, built from its dimensions, which turns the strike density into ND, the expected strikes per year.
Construction, contents, occupancy, consequence
Four coefficients describing what the structure is built from, what it holds, who uses it and what a strike would cost. Together they set NC, the tolerable strike frequency it is judged against.
A critical facility, a hospital, a fire station or a power plant among them, should be protected or carried through the detailed assessment whatever the simplified risk assessment shows. That clause applies on top of the assessment, not instead of it.
Four kinds of loss, each judged on its own
The detailed assessment never sums the risks into one verdict. R1 to R3 each meet their own tolerable line from Table L.6.2, R4 meets a value the owner enters, and a structure can fail on one while passing the rest.
R1 · life or injury
Loss of life or injury
Judged against the default tolerable value in Table L.6.2, the strictest of the four. The owner or the authority having jurisdiction may set a different value.
R2 · service
Loss of service
The risk that a strike interrupts a service the structure depends on, defaulting to the tolerable value in Table L.6.2.
R3 · historical significance
Loss of historical significance
For a structure of historical or cultural value, judged against its default tolerable value in Table L.6.2, the same default as loss of service.
R4 · economic value
Loss of economic value
Eight components, from the structure and its services
Every risk is built from these eight components, each a source of strikes paired with what it puts at stake.
| Component | Where the strike lands |
|---|---|
| RA, RB, RC | A direct strike to the structure itself |
| RM | A strike near the structure, not a direct hit |
| RU, RV, RW | A direct strike to a connected service, summed per service |
| RZ | A strike near a connected service, summed per service |
A small metal building, settled by the simplified risk assessment
An illustrative structure, computed by Sphera through the simplified risk assessment, with each step named by its clause.
20 m by 15 m, 6 m high, standing alone
- Lightning ground strike-point density NSG of 2 per km² per year (L.2), isolated, so CD is 1 (Table L.4.2)
- Metal structure with a metal roof: C2 of 0.5
- Low-value contents: C3 of 0.5. Normally unoccupied: C4 of 0.5
- Services can stop without harm: C5 of 1.0 (Tables L.5.1.2(a) to (d))
ND is below NC, so an LPS is optional
- Collection area AD of about 2,578 m², equation (L.4.1.1)
- Expected strikes ND of 0.0052 per year, equation (L.3)
- C = C2 × C3 × C4 × C5 = 0.125, so the tolerable NC is 1.5 × 10⁻³ ÷ 0.125 = 0.012 per year (L.5.1.1)
- 0.0052 does not exceed 0.012, so protection is optional
Had ND come out above NC, an LPS would be recommended, and a critical facility goes on to the detailed assessment whatever the comparison shows. The values are illustrative; your figures depend on your own structure and site.
What goes into the document you sign
One assessment produces a report carrying the verdict, the simplified risk assessment with its working, and the detailed assessment broken into the strikes to and near the structure, the risk components, the probabilities and shielding factors, and the loss factors behind each figure.
Read a full report before you start a trial: a worked example for an office block in Tampa, computed to NFPA 780-2026 through the simplified risk assessment and the detailed assessment.
Download the sample reportKnow when each site is due for a look
-
Available today
Review dates, inspection dates and reminders
The engineer sets when an assessment is looked at again. Each tracked protection system keeps its own inspection due dates. An email goes out two months before each date and again on the day.
-
Available today
Periodic inspection reports
Plan each visit, then record the checklist, the readings at each test point and any defects. A reviewer signs it off, and you issue the inspection report and the protection system's evidence pack.
Lumi speeds the routine. Sphera still owns every number
You just read that procedure, computed clause by clause. Lumi works around Sphera to cut the busywork, with the signing engineer in control at every step.
Risk-driver analysis
Reads the completed assessment and shows which component drives each risk, so you know exactly where to act.
Drafted report narrative
Turns your computed figures into clear report prose you review, edit and approve before it is filed.
The least protection that complies
Tries combinations of protection measures and proposes the one that brings R1 to R4 within their tolerable values, with each risk before and after.
Guides for this standard
Methods
Comparisons
Free tools
Free calculators built on the standard's own equations, each citing the clause behind its result.
Rolling sphere method calculator
A free calculator for the protected radius of a single mast, with IEC 62305, NFPA 780 and AS 1768 sphere radii in feet or metres.
NFPA 780 risk assessment calculator
A free Annex L screen: compare the yearly strikes to the structure, N_D, with the tolerable frequency N_C, with every step cited to NFPA 780-2026.
NFPA 780-2026 in Lumex™, questions answered
Which edition of NFPA 780 does Lumex™ run?
What do I enter for an NFPA 780 assessment?
What is the difference between the simplified and the detailed assessment?
When should I run the detailed assessment?
What tolerable values does Lumex™ use?
Does Lumex™ recommend the protection?
How is the NFPA 780 engine checked?
What goes into the NFPA 780 report?
When is an NFPA 780 assessment due for review?