Method

IEC 62305-2: the risk assessment method

Part 2 is the part of the standard that decides whether a structure needs lightning protection. It builds the risk R, which covers injury to people and physical damage, plus a separate frequency-of-damage measure, from the building, its surroundings and its connected lines, compares them against a tolerable level, and shows exactly which protection measures bring them into line.

An engineer working through an electrical diagram beside a control panel

IEC 62305-2 is the risk management method behind every IEC 62305 assessment.

It is the part of the standard that decides one thing: does this structure need lightning protection, and if so, how much. It answers that not with a fixed rule applied to every building, but by turning the structure, its surroundings and its connected lines into a risk of injury to people and a separate frequency-of-damage measure, and checking each against a level the standard is prepared to tolerate.

That risk-based approach is what makes the method defensible. Two buildings of the same size can reach opposite verdicts because one sits on an exposed ridge in a high-lightning region while the other is sheltered in a low-activity area, or because one houses a crowd and flammable stock while the other is an empty warehouse. The method is built to capture those differences and put a number on them. This guide walks through R and the frequency of damage, how each is built from components, where the numbers come from, how protection lowers them, and what the 2024 third edition changed. New to the standard as a whole? Start with what is IEC 62305.

What the method produces

A risk of injury to people, and a frequency of damage

The 2024 third edition produces two figures. A single risk of injury to people, judged against a tolerable risk, decides whether protection is needed; a separate frequency of damage measures how often a strike would disrupt the internal systems.

Risk R

Injury to people, death included

Injury or death from touch and step voltages, and from fire, explosion and the failure of life-safety systems after a strike, all combined into one risk. R carries the strictest tolerable limit, the tolerable risk RT, for which clause 7.3 NOTE 1 gives 1×10-5 per year as a representative value that your jurisdiction may replace. On most projects it is the figure that decides whether protection is needed.

Frequency of damage F

Availability of internal systems

How often a strike would disrupt the internal electrical and electronic systems, judged against a tolerable frequency FT. It is the figure that leads where keeping the electronics running is the point, such as a data centre, a control room or a telecom site, rather than the threat to people.

Both figures are built from the nine risk components RAT, RAD, RB, RC, RM, RU, RV, RW and RZ. The 2024 edition recognises three kinds of loss, L1 to L3: injury to human beings, physical damage to the structure and its contents, and failure of internal systems. These are the loss categories the assessment weighs, not separately gated risks. The pass or fail verdict turns on the risk R against RT, and on the frequency of damage F against FT. The 2010 edition also carried a cultural heritage loss and a purely economic loss that could be weighed on cost and benefit; the 2024 edition removed both.

How a risk is built

Components: a source paired with a type of damage

No risk is a single number you read off a chart. Each one is the sum of components, and every component describes a specific way a strike can harm the building. A component pairs a source of damage, meaning where the strike lands, with a type of damage, meaning what that strike then does. Splitting the problem this way is what lets the method credit a protection measure precisely: a surge arrester helps against an induced surge on an incoming line but does nothing for a person standing next to a down conductor, and the component structure keeps those effects apart.

The four sources of damage (where the strike lands). A direct flash to the structure itself (S1), a flash to the ground near the structure (S2), a flash directly to a service line that enters the building such as power or telecoms (S3), and a flash to the ground near such a line (S4). The direct and near hits threaten the structure in different ways, and the two line sources matter because a surge travels in along the cable from well outside the building.

The three types of damage (what the strike does). Injury to living beings from touch and step voltages (D1), physical damage such as fire, explosion or mechanical destruction (D2), and failure of internal electrical and electronic systems caused by the electromagnetic pulse the strike radiates, known as LEMP (D3). One strike commonly causes more than one type at once, which is why a single source can feed several components.

Pairing the sources and the types gives the set of components that make up each risk. A direct flash to the structure can hurt people (D1), set it alight (D2) or fry its electronics (D3); a flash near a line mainly drives a surge that causes an internal failure (D3). The method adds the components that apply to the risk in question, which is why a structure with no connected lines, or no people inside, simply drops the components that cannot occur.


The chain

Every component is rate, probability and loss

Each component follows the same three-step chain, and it is worth holding this in mind because it is what a protection measure acts on. A component equals how often a dangerous event occurs, multiplied by the probability that the event causes the damage in question, multiplied by the loss that results. Written plainly: rate times probability times loss.

The first term, the rate, is a frequency: how many dangerous events of that kind happen per year, driven by the lightning activity of the location and the area that collects strikes. The second, the probability, is between zero and one: given the event, how likely it is to actually cause that damage, which is exactly where protection bites. The third, the loss, scales the consequence: the fraction of value, people or service lost when the damage does occur. Multiply the three, sum the components, and you have the risk for that loss type.

This is the lever the whole assessment turns on. A measure that halves a probability halves that component. A measure that cuts the loss, such as fire compartmentation, shrinks the consequence without touching how often strikes land. The method makes both visible, so the report shows not just the final number but which term each measure moved.


Where the rate comes from

Collection areas and the dangerous-event rate

A strike does not have to hit the building to count. A structure and each line connected to it gather flashes from a zone of ground around them, called the collection area. The taller and larger the exposed object, the wider that zone: a tall mast on a hill draws flashes from a much bigger area than a low building on a plain, because its height lets it intercept strikes that would otherwise have hit the ground nearby. The method works out a collection area for direct flashes to the structure (Ad), for flashes near the structure (Am), for flashes to each line (Al) and for flashes near each line (Ai). The idea is the same in every case: estimate the patch of ground from which that object pulls strikes.

The rate of dangerous events is then the local lightning activity multiplied by the collection area, adjusted by a location factor that accounts for shielding from nearby structures, trees and terrain. A building hemmed in by taller neighbours collects far fewer direct strikes than the same building standing alone, and the location factor is how the method credits that. For the line sources, the rate also reflects the length and type of the line and whether it runs overhead or buried, since a long overhead power line is exposed to far more flashes than a short buried cable.

The local lightning activity is the input that ties the whole assessment to a place. In the 2024 third edition this is the ground strike-point density, written NSG, the number of points struck per square kilometre per year. This replaces the older flash density, NG, used by earlier editions. The change is not cosmetic: a flash can have several ground strike points, so the new measure describes the hazard a structure actually faces more accurately, and it can shift the computed rate enough to change a verdict. Wherever you take the figure from, it should reflect the real location, since the rate scales directly with it.


Where protection bites

Probabilities of damage, and how measures lower them

The probability term is the heart of the design conversation, because it is mostly what protection changes. Given that a dangerous event has occurred, the probability says how likely it is to actually cause the damage in question. Without protection these probabilities sit high. The job of a protection measure is to pull them down, and the method gives explicit credit for doing so.

Physical damage from a direct strike. Fitting a lightning protection system lowers the probability that a direct flash causes physical damage, and the higher the class of system the more it lowers it. An LPS of class I, the most demanding, intercepts the widest range of strike currents and substantially reduces that probability; a class IV system reduces it less. The class follows the lightning protection level (LPL I to IV) the assessment computes, so the level chosen feeds straight into the risk through this probability.

Failure of internal systems. Coordinated surge protective devices lower the probability that an induced surge knocks out the electronics inside. Coordination matters: SPDs at the service entrance and at the equipment work together so that what gets past the first is clamped by the next, and the better the coordinated set, the lower the probability of an internal failure. Shielding, careful routing and bonding reduce it further by cutting the surge the wiring picks up in the first place.

Injury to people. The probability of injury from touch and step voltages is reduced by physical measures around the structure, such as insulation, equipotential bonding, restrictions and warnings near down conductors, and the layout of the earth termination. These act on the D1 components without changing how often strikes arrive.

The point throughout is that protection is credited where it physically helps and nowhere else. An LPS does not lower the probability of an internal surge failure; SPDs do not stop a direct strike setting a roof alight. Keeping the probabilities separate per component is what lets the method recommend the right combination rather than over-specifying one measure to cover risks it cannot touch.


Scaling the consequence

Loss factors: how much is actually at stake

The same strike on the same building can cost very different amounts depending on what is inside and who is present, and the loss term is how the method captures that. The loss scales the consequence of each component: the fraction of what is at stake, life, the structure and its contents, or the function of the internal systems, that is lost when the damage occurs. It is what separates a strike on an empty store from one on a packed venue with flammable stock.

Loss rises with the people exposed and with special hazards. A structure holding a crowd, or one with a risk of explosion or a hard-to-evacuate occupancy, carries a much larger loss for physical damage than a sparsely occupied building, and the method increases the loss factor accordingly. Conversely, measures that limit the spread of harm reduce the loss: fire detection and suppression, compartmentation that stops a fire crossing the building, and bonding and protective measures that reduce the reach of touch and step voltages all cut the fraction lost when damage happens. Because the loss multiplies the rate and probability, reducing it is a legitimate route to bringing a risk down even where the strike itself cannot be made less likely, which is exactly the case for many existing buildings.


The verdict

Tolerable risk decides it, then you add measures

With every component computed and summed, each figure is compared against its tolerable value. The risk of injury to people R is judged against a tolerable risk RT, and the test is simple: a risk at or below its tolerable value passes, and a risk above it means the structure needs protection. The frequency of damage F is checked the same way against its tolerable frequency FT. Those two comparisons are the whole verdict.

The value that decides is not a fixed one. Clause 7.3 NOTE 1 gives RT = 1×10-5 per year as a representative value of tolerable risk and adds that another value may be set once the case has been investigated in detail. Printed p.12 then lets national or local regulations fix RT, the tolerable frequency of damage FT, and the Annex A, B, C and E calculation rules and parameter values. Which value applies is a property of the jurisdiction the structure sits in, so a Lumex assessment states it explicitly. The 2010 edition additionally weighed a purely economic loss on cost and benefit, with no tolerable line; the 2024 edition removed that loss type, and its Annex D now covers the evaluation of PSPD instead.

Where a risk fails, the assessment is iterative. You add the measures that act on the dominant components, recompute, and check again, repeating until each risk sits below its tolerable value. Because the method shows which components carry most of the risk, the choice of measure is targeted rather than a blanket specification: if the risk is dominated by internal-system failure, coordinated SPDs do the work; if it is dominated by physical damage and life safety, an LPS of the right class and fire measures are what move the number. The output is a clear, defensible verdict for each risk, with the reasoning traceable back to the clause and the components behind it. This traceability is what an auditor, an insurer or an authority looks for, and it is what a manual spreadsheet most often fails to show.

From method to design

How protection measures map onto the chain

Each measure the standard recognises acts on a specific term of a specific set of components. Reading them this way is what turns a failed risk into a defensible design.

Lightning protection system (LPS)

Captures a direct strike and leads it safely to earth, lowering the probability of physical damage. A higher class, class I being the most demanding, lowers it further. It acts on the direct-strike components, not the line surge ones.

Coordinated SPDs

Surge protective devices at the service entrance and at the equipment lower the probability that an induced surge causes an internal-system failure. Their coordination, not just their presence, is what the method credits.

Fire and physical measures

Detection, suppression and compartmentation reduce the loss when a fire follows a strike, scaling down the consequence of the physical-damage components rather than how often they occur.

Bonding and earthing

Equipotential bonding and the earth-termination layout reduce both the probability of injury from touch and step voltages and the chance of dangerous sparking inside, acting across the life-safety and physical-damage components.

Shielding and routing

Spatial shielding, screened cables and careful routing cut the surge the internal wiring picks up, lowering the probability of internal failure before the SPDs ever act.

Thunderstorm warning systems

Recognised in the 2024 edition as a risk-reduction measure: by triggering temporary precautions before a storm, they lower the probability of harm to people during the period of greatest exposure.

Current edition

What the 2024 third edition changed in the method

The third edition, published in 2024 and adopted nationally across most of the world, is the version an auditor or authority cites today, and it changes the method in ways that can flip a verdict. Building on a 2010-era spreadsheet is not just out of date, it can compute a different answer.

The most consequential change is the move to a ground strike-point density, NSG, in the dangerous-event rate, in place of the older flash density. Because a single flash can strike the ground at more than one point, this describes the real hazard more faithfully and can raise or lower the computed rate. The edition also brings injury to people and loss from fire into a single combined risk view, so the two are no longer assessed in isolation from each other. It adds a frequency-of-damage measure aimed at the availability of internal systems, recognising that for some sites keeping the electronics running is itself the thing being protected. And it formally recognises thunderstorm warning systems, in line with IEC 62793, as a measure that reduces risk by enabling temporary precautions ahead of a storm. Each of these can change which measures a structure needs, which is why the edition an assessment is built on is part of the result, not a footnote.


Run it

From the method to a filed report

The method is exact but unforgiving by hand: dozens of components, each with its own collection area, rate, probability and loss, all recomputed every time a measure is added or a dimension changes. Lumex runs the full IEC 62305-2 method on the building you describe, computes every component, compares each risk against its tolerable value, and shows which measures bring a failing risk into line, with the reasoning traceable clause by clause. To see the chain end to end with an illustrative worked example, follow the numbers on one building, read how an IEC 62305 assessment works, or explore the platform.

New to the standard? Start with what is IEC 62305, or see which structures need an assessment and the types of loss it weighs. Once an LPS is installed, Part 3 governs its periodic inspection and testing, the maintenance cycle that keeps an assessment valid.

FAQ

Questions answered

What is IEC 62305-2?

IEC 62305-2 is the risk management part of the IEC 62305 lightning protection standard. It is the part that decides whether protection is needed. It defines a method that turns a structure, its surroundings and its connected lines into a risk of injury to people (R) and a separate frequency of damage (F) to internal systems, then compares each against a tolerable level. Protection is only required where a risk exceeds what the standard accepts.

How does IEC 62305-2 decide whether a structure needs protection?

The 2024 third edition produces a single risk R, which combines injury to people and loss from fire, and judges it against the tolerable risk R_T. Clause 7.3 NOTE 1 gives 1×10⁻⁵ per year as a representative value of R_T, not a fixed one, and national or local regulation may fix a different value. Alongside it, a separate frequency of damage, F, measures how often a strike would disrupt the internal electrical and electronic systems, judged against a tolerable frequency F_T. Both are built from the nine risk components R_AT, R_AD, R_B, R_C, R_M, R_U, R_V, R_W and R_Z. Protection is required where R exceeds R_T, or where the frequency of damage exceeds what the site can tolerate. The 2024 edition weighs three types of loss. L1 is injury to people, death included. L2 is physical damage to the building and what it holds. L3 is failure of the systems inside it. These are the kinds of loss the assessment weighs, not separately gated risks.

What are the risk components in IEC 62305-2?

Each risk is the sum of components. Every component pairs a source of damage with a type of damage. The four sources are a direct flash to the structure (S1), a flash near the structure (S2), a flash to a connected line (S3) and a flash near a line (S4). The three types of damage are injury from touch and step voltages (D1), physical damage such as fire or explosion (D2), and failure of internal electrical and electronic systems from the electromagnetic pulse, LEMP (D3). Each component equals how often a dangerous event occurs, multiplied by the probability it causes that damage, multiplied by the resulting loss.

How does IEC 62305-2 work out how often lightning will strike?

The method works from the lightning activity of the location and the area that collects strikes. A structure and each connected line gather flashes from a zone of ground around them, called the collection area, which grows with the size and height of what is exposed. The number of dangerous events per year is the local ground strike-point density multiplied by that collection area, adjusted by a location factor for nearby structures and terrain. The 2024 edition uses a ground strike-point density in place of the older flash density.

How do protection measures lower the calculated risk?

Protection measures act on the chain inside each component. A lightning protection system lowers the probability of physical damage from a direct strike, and a higher LPS class lowers it further. Coordinated surge protective devices lower the probability that an induced surge causes an internal-system failure. Fire measures, compartmentation and bonding reduce the loss when damage does occur. Thunderstorm warning systems reduce the probability of harm to people by triggering temporary precautions ahead of a storm. The assessment adds measures until each risk falls below its tolerable level.

What is the tolerable risk in IEC 62305-2?

The tolerable risk, R_T, is the highest risk of injury to people accepted for the structure. It is not a fixed constant. Clause 7.3 NOTE 1 gives R_T = 1×10⁻⁵ per year as a representative value and allows another value once the case has been investigated in detail, weighing how exposed the people inside and around the building are and how much the public depends on it. National or local regulation may fix R_T, the tolerable frequency of damage F_T and the Annex A, B, C and E rules and parameter values, so the value that applies is a property of the jurisdiction, with the representative figure as the default where nothing else is specified. The whole purpose of the assessment is to bring the computed risk of injury to people R below whichever R_T applies, with the smallest set of measures that does the job. The availability of internal systems is handled separately, through the frequency of damage F judged against a tolerable frequency F_T. Under the 2024 edition it is the frequency of damage that covers pure economic loss and loss of service; the 2010 edition's separate economic loss type, weighed on cost and benefit with no tolerable line, no longer exists.

Is lightning protection always required under IEC 62305-2?

No. The method is risk-based, not prescriptive. It can show that a structure already sits below the tolerable risk, in which case no protection is required and the assessment records why. Protection is specified only where a computed risk exceeds the tolerable level, and the assessment identifies exactly which measures bring it back into line.

What changed in the 2024 third edition of IEC 62305-2?

The third edition moves the dangerous-event rate onto a ground strike-point density rather than the older flash density, brings injury to people and loss from fire into a single combined risk view, adds a frequency-of-damage measure aimed at the availability of internal systems, and recognises thunderstorm warning systems, in line with IEC 62793, as a measure that reduces risk. Each of these can change whether a given structure passes or needs protection, so the edition an assessment is built on matters.

What information does an IEC 62305-2 assessment need about a building?

It needs the structure's dimensions and height, its location and the local lightning activity, the surroundings and terrain, the construction and roof materials, the contents and the people present, the services that enter it such as power and telecoms, any special hazards such as flammable or explosive contents, and any protection already in place. From this the method derives the collection areas, dangerous-event rates, probabilities and losses for every component.

What Lumex does, and what stays with you

Lumex computes the IEC 62305-2 method and shows the working. It does not certify a structure. You may not issue or submit a Lumex output until a competent person, qualified where the structure is located, has reviewed the inputs and the result and signed it.

The tolerable risk in IEC 62305-2 is not a fixed constant. Clause 7.3 NOTE 1 gives RT = 1×10-5 per year as a representative value of tolerable risk and adds that another value may be set once the case has been investigated in detail. Printed p.12 then lets national or local regulations fix RT, the tolerable frequency of damage FT, and the Annex A, B, C and E calculation rules and parameter values. Every Lumex assessment states the jurisdiction it was computed under and the values that applied.

Get started today

See the 62305-2 method run on your own building

Contact our team